Jubang Electric Company
|
Price: | 10.9~481.0 USD |
Payment Terms: | T/T |
Place of Origin: | Zhejiang, China (Mainland) |
Add to My Favorites | |
HiSupplier Escrow |
Rated frame current | 63 | 100 | 225 | 400 | 630.800 | 1250 | |||||||||||
Model | GTM2-63 | GTM2-100 | GTM2-225 | GTM2-400 | GTM2-630 GTM2-800 | GTM2-1250 | |||||||||||
Rated current | 6.10.16.20.25. 32.40.50.63 | 16.20.25.32.40 50.63.80.100 | 100.125.140.160. 180.200.225 | 200.250.315 350.400 | 400.500.630 700.800 | 630.700.800. 1000.1250 | |||||||||||
Poles | 2.3.4 | 2.3.4 | 2.3.4 | 3.4 | 3.4 | 3 | |||||||||||
Rated insulating current Ui | 660 | 800 | 800 | 800 | 800 | 800 | |||||||||||
Rated operating Voltage Ue | 440 | 690 | 690 | 690 | 690 | 690 | |||||||||||
Operating times | on | 6000 | 6000 | 2000 | 1000 | 500 | 500 | ||||||||||
off | 8500 | 8500 | 7000 | 4000 | 2500 | 2500 | |||||||||||
Breaking capacity grades | S | H | S | H | R | S | H | R | S | H | S | H | R | S | H | ||
Rated ultimate short circuit breaking capacity Icu(KA) | 690V | / | 10 | 8 | 20 | / | 8 | 20 | / | 10 | 20 | 10 | 20 | / | 20 | 25 | |
400V | 25 | 50 | 35 | 50 | 85 | 35 | 50 | 85 | 50 | 65 | 50 | 65 | 100 | 65 | 100 | ||
Rated operating short circuit breaking Capacity Ics(KA) | 690V | / | 5 | 4 | 10 | / | 4 | 10 | / | 10 | 10 | 10 | 10 | / | 18 | 20 | |
400V | 18 | 35 | 25 | 25 | 42.5 | 25 | 35 | 42.5 | 35 | 40 | 35 | 40 | 50 | 32.5 | 40 | ||
Outline dimensions | L | 135 | 135 | 155 | 155(155) | 165 | 165(165) | 257(257) | 257(257) | 330 | |||||||
W | 76 | 76 | 90 | 90(120) | 105 | 105(140) | 140(183.5) | 210(280) | 210 | ||||||||
H | 73.5 | 81.5 | 68 | 86(86) | 86 | 103(103) | 103(103) | 103(103) | 137 | ||||||||
Installation dimensions | A | 117 | 132 | 126 | 194 | 243 | 299 | ||||||||||
B | 25 | 30 | 35 | 44 | 70 | 70 | |||||||||||
d | 3.5 | 4.5 | 5 | 7 | 7 | 9 |
HS Code: | 85362000 |
---|
Standard: | Iec 60947-2 |
---|